Skip to content

NFPA 96

Laws and regulations regarding fire safety can be complex. There’s a lot to consider to maintain compliance and safety. Here’s some information you may find helpful. 

services-1

NFPA 96

NFPA is the governing body that establishes regulations for the commercial fire industry. NFPA 96 includes the regulations for commercial kitchen owners and operators. Below are some regulations and a chart laying out how cleanings should be scheduled based on cooking patterns.

11.3 Inspection Of Exhaust Systems

The entire exhaust shall be inspected by a properly trained, qualified, and CERTIFIED company or person (s) acceptable to the authority having jurisdiction in accordance with Table 11.3

Table 11.3 Exhaust System Inspection Schedule

Type or Volume of Cooking Frequency Frequency

Systems serving solid fuel cooking operations. MONTHLY

Systems serving high-volume cooking operations such as 24-hour cooking, charbroiling, or wok cooking. QUARTERLY

Systems serving moderate-volume cooking operations. SEMIANNUALLY

Systems serving low-volume cooking operations, such as churches, day camps, seasonal businesses, or senior centers. ANNUALLY

 

services-2
services-4

11.4 Cleaning Of Exhaust Systems

Upon inspection, if found to be contaminated with deposits from grease-laden vapors, the entire exhaust system shall be cleaned by a properly trained, qualified, and CERTIFIED individual acceptable to the authority having jurisdiction in accordance with Section 11.3.

11.4.2

Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to bare metal prior to surfaces becoming heavily contaminated with grease or oily sludge.

Play Video